Variation in Riser Flow for Wide Solar Water Heating Collectors

 

This is a test to get an idea how much variation in flow there is between the risers in a wide collector. 

 

The motivation for the test was that 1) there seems to be little data out there confirming that this manifold arrangement actuall does distribute fluid evenly to all of the risers, and 2) a poor distribution was reported on one collector of this type...

 

The test collector is has a bottom manifold (supply) and a top manifold (return) connected by many vertical risers that are spaced about 6 inches apart. 

The intent of this design is to distribute the heat transfer fluid equally among the risers so that each riser receives the same flow.

 

The collector used for the test is my 93.3 sf, 11 ft wide collector:

133 inches wide by 101 inches high -- 93.3 sf.

 

Risers are half inch copper and about 100 inches long -- 20 risers in all spaced at about 6 inches.

 

Manifolds (top and bottom) are 3/4 inch copper, and about 130 inches long.

 

Risers are connected to manifolds with standard copper 3/4 by 1/2 inch reducing T's.
(these reducing T's are used at all riser locations, including the first and last riser)

 

Water enters the collector at the lower right by 3/4 inch copper supply pipe.
Water exits the collector at the upper left by 3/4 inch copper return pipe.

Vertical rise from tank water level to top of collector is 9.9 ft

Collector with glazing off showing manifolds, risers, and supply and return

 

 

It is difficult to measure the actual flow in each riser directly (anyone have a good idea on how to do this?).  So, I took the approach of removing the glazing, and taking temperature measurements at the bottom, middle, and top of each riser.  Risers that are being fed with a good supply of water should show a progressive rise in temperature from top to bottom, with the bottom temp not much higher than the supply water (tank) temp.  Risers that are getting low or no flow should show little change in temperature, and high temps, since the water flow is not removing heat from them.

 

This is not a perfect test in that the collector glazing has to be removed to take the temperatures, breezes effect temp readings a bit, it takes 8 minutes to do a full set of readings (so things may vary a bit), and the IR temp gun just has a little reading to reading variation.  So, don't over interpret differences of a couple degrees -- it may just be the test setup variation.  The test does appear to be good enough to pick up serious flow distribution discrepancies.

 

To do the test, I lowered the tank temp, which was at 149F down to about 110F by running the pump overnight. This was necessary as, with the glazing off, the collector would lose heat with 149F rather than gaining heat.

 

The top 10 inches of the collector is shaded by the roof eave at this time of year -- this combined with the vertical tilt keeps it from overheating when stagnated even with the Twinwall glazing.

 

 

Click on pictures for full size


Collector with before glazing was removed

Collector with glazing removed for test.

 

 

 


Upper left corner of collector.
The elbow and union are part of
the return plumbing.

Upper right of collector.
The white painted thing on the end is
a regular copper end cap.

Lower left of collector.
Terminated with copper cap.

Lower right of collector.
The supply is the vertical pipe coming
in from below via the elbow.

 

 

Results

The table shows the results of measuring the temperature of each riser at the bottom, middle, and top with flow through the collector and with the glazing off.

 

The bottom temp measuring point was 8 inches above the lower manifold, and the upper temp was measured at 14 inches below the top manifold (about 4 inches below the shadow that is shading the top 10 inches of the collector).  The middle reading was taken half way between the upper and lower points.

 

 

Riser No 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
top 124 123 123 124 126 129 124 128 126 132 127 125 129   125 128 126 123 123 122
mid 123 122 121 123 124 124 120 125 123 125 125 125 125   124 123 123 123 123 120
bottom 122 117 119 117 119 117 115 119 118 119 120 121 119   117 117 115 116 120 115
                                         
Time 12:47 PM                                     12:56 PM
                                         
Temp rise 2 6 4 7 7 12 9 9 8 13 7 4 10 0 8 11 11 7 3 7

 

 

So, the distribution (to me) seems pretty even.

 

There is some variation in the temp rise in the various risers, but no really dramatic differences.

 

The far left riser does appear to be getting more flow.  This may be real, as it also showed up on one other run, but the bottom of riser temp of 122F looks a bit suspect.  Another factor may be that the left most and right most risers are trimmed a bit in width to fit inside the case -- so, they probably get a little less gain that other risers.

On the two other runs I did, the left riser had a more normal rise on one of them (6F), and a low temp rise in the other.

 

Sun conditions were very clear. 

There was a light and variable breeze, which may effect temperature readings a bit.

 

From the differential controller readout:

Tank temp bottom = 110.6F

Tank temp top = 111.7 F

Tcollector = 127.9F  (as reported by the differential controller)

All of this was done with the pump turned on with a flow rate of 4.6 gpm (0.049 gpm/sf).

The pump is a Grundfos 15-58 3 speed pump on low speed.

 

The pump is mounted just outside the tank at a level about 30 inches below the water surface. 

A 3/4 inch copper U-tube connects the pump inlet to the water near the bottom of the tank.

 

The supply run of 3/4 inch copper is probably only about 8 ft from pump to bottom of collector. 

The return line is also 3/4copper, and is about 20 ft long.

All plumbing is sloped toward the tank.

The return line ends inside the tank in the airspace above the water.

 

Before the pump was turned on, but after the glazing was removed, the absorber temp ranged from 128F up to 140F.

 

In the course of 3 runs with the glazing removed, the tank temp went up about 2F -- so, even with the glazing off, it was collecting heat.

 

Bonus Data

Since I had to take the tank lid off to measure flow rate (having forgotten the previous measurement).  I went ahead and took these measurements at each of the 3 speeds of the Grundfos 15-58 pump:

 

Pump speed Flow rate
gpm
Flow Rate/sf Power
watts
Time to full flow
seconds
drain back time
seconds
Low 4.6 0.049 59 50 28
Med 6.4 0.068 75 35 28
High 7.5 0.08 87 30 30

 

Even at the low speed, the 15-58 provides a good brisk flow rate, which is precisely in the middle of the range recommended by Heliodyne for their collectors (0.025 to 0.075 gpm/sf).

 

The 14 ft static head at low speed filled the collector and established full flow conditions without any hesitation or difficulty clearing air.

This static head is 40% greater than the actual vertical head from tank level to top of collector.

 

Flow measurements were taken by timing how long it took to fill a half gallon container with a stop watch.

Power measurements with a KillAWatt meter.  For comparison, the power consumption numbers in the Grundfos spec are 60 watts low speed, 80 watts mid speed, 87 watts high speed.

 

 

In the pump curves below, the 15-58 is the one marked "A" -- 14 ft static head at low speed.

 

 

 

 

 


Thom's Collector

 

This test was done as a result of the uneven distribution of fluid to the risers on Thom's 24 ft wide collector.  When Thom did the same measurements his collector shows a pattern of lots of flow in the end risers, but little flow in the middle risers.   Thom's collector is done as two 12 ft wide collectors -- each of the 12 ft wide collectors is very similar to my 11 ft wide collector.

 

Its still not clear what the reason for this the poor flow distribution in Thom's collector, in that his collector is built in very much like mine.  Two potential differences come to mind: 1) on Thom's collector, the end riser is connected to the manifold with an elbow rather than a reducing T, and 2) even with a garden hose hooked up to supply more pressure, Thom's flow rate to half of his collector (which is similar in size to my full collector) is only 2.5 gpm.

 

The connection of the end risers with elbows rather than T's seems like a small issue, but this earlier test indicates it might have a significant effect.

 

We are still trying to work out why Thom's collector is showing such a larger variation in riser flow.  These are the discussion threads on SolarHeat and Simply Solar groups.  If you have any ideas on this, please post them.

 

SolarHeat post...

 

Simply Solar post...

 

 

 

Gary August 19, 2010