Test on Downspout Solar Air Heating Collector

There has been an ongoing question on the Yahoo Simply Solar discussion group about how much solar heat gets transferred around to the back surface of the solar air heating collectors made from gutter downspouts.  If a significant amount of solar heat gets transferred around to the back so that the back,  front and sides of the downspout collector are all hot, then this increases the absorber to air heat transfer area, which is a major consideration on solar air heating collector.

In the downspout collector design, ordinary aluminum downspouts are laid side by side (or sometimes spaced apart a bit) to form the absorber.  Sun shines on one side of the downspout heating it up.  Air is forced through the downspouts and picks up heat from the hot downspout metal and delivers it to the house.

If you want to see what a downspout collector looks like -- there are a couple good examples on Scott's site...

One of the difficult design issues with solar air heating collectors is providing good heat transfer between the solar heated absorber and the air.  Air is light in weight and low in heat capacity, so a lot of air needs to be passed through an air heating collector, and it has to be done in a way that puts a lot of the air in good thermal contact with the absorber.  Downspouts are thought to have an advantage here in that they provide a large heat transfer area from absorber to air.  But, this is only true if the solar heat gets transferred around the downspout sides and back.  This test is aimed at finding out how well the downspout does in transferring heat around to the sides and back.

The Test Setup

The picture below shows the not so ambitious test setup. 

There are 3 aluminum gutter tubes about 31 inches long each.  They are spaced about half an inch apart.  Each is foamed into an air supply plenum made from rigid foam board insulation.
A small bathroom vent fan delivers air to the plenum.
Some 1 inch rigid foam board is used to cover the back side of the collector and the east and west sides of the outer tubes.  The insulation is made so that it can be very quickly removed to measure the temperatures of the back of the tubes.  The idea of the insulation board is to keep the heat loss from the back of the downspouts to the ambient air small, and more closely simulate a real collector.

The temperature of the air coming into the fan, and the outlet temperatures for the two outer downspouts were measured.  The exit velocity of the airstream was measured for all three tubes with  a Kestrel wind meter. 
A thermal camera was used to get the temperatures of the front and back.  This was done by taking a thermal picture of the front, then moving around to the back and quickly removing the back insulation and taking a thermal picture of the back.

test setup for downspout collector test test setup

The picture on the right shows the three tubes glued into the plenum, but without the back insulation panel installed.

The picture on the left shows how the "collector" was setup during the actual test.  It was run this way for several minutes until temperatures stabilized, and the the front thermal image was taken, the back insulation was quickly removed and the back insulation picture was taken.

The downspouts measure 2 inches by 3 inches and are 0.016 inch thick aluminum.

 

sun side of absorber
Thermal image from sun side after it stabalized.
back side absorber
Thermal image from back (north) side taken at same time as image to left.

The left picture shows the collector from the front (sun side).  Temperature of the west tube is 96.2F on top, 94.3 half way down, and 77.2F near the bottom.  Remember, the west tube is on the left in the front pic, and on the right in the back pic.

The right picture shows the collector from the back at the same time as the left picture, and immediately after the back insulation board was removed.  The corresponding west tube temperatures on the back are 91.17F at the top, 81.5F in the middle, and 70.5F near the bottom.

Both thermal images are adjusted to show a temperature range of 50F up to 105F, so areas of the same color have the same temperature in both pictures.  The "Sp" boxes show actual temperatures at those locations.  The images were taken with an FLIR I7 IR camera.  Just from the thermal pictures, its pretty clear that some heat is getting around to the back. 

The temperatures are different on each tube because they were getting quite different amounts of airflow. 

The fan inlet air temperature was 56F.

For the west tube, flow rate was 240 fpm (10 cfm), and the air outlet temp was 68.7F (front metal temp here is 96.2F)

For the east tube, flow rate was 690 fpm(28.8cfm), and the air outlet temp was 63.6F (front metal temp here is 85.2F)

Flow rate in the middle tube was 510 fpm (21.3cfm).

Kind of makes you wonder how good a job plenums do in evenly distributing airflow to multiple tubes :)

So, the table just below shows the temperatures measured at corresponding places at the front and back on the west tube, and shows the estimated air temperatures at the same locations.

  Front of Collector
West Tube (F)
Back of Collector
West Tube (F)
Temperature Drop
Front to Back (F)
Estimated West Tube
Air Temperature (F)
Near top 96.2 91.1 5.1 68.7
Midway down 94.3 81.5 12.8 62.5
Near bottom 77.2 70.5 6.7 56
         

If you assume that the heat transfer is proportional the the temperature difference between the metal and the air, then the heat transfer rate on the on the back side of the downspout averages about 0.7 as much as the heat transfer on the front (sun) side of the absorber.

The sides of the gutter also add to the heat transfer area and probably actually run a little warmer than the back, so they also make a good contribution to the heat transfer area.

On a separate run, the following temps were recorded in a similar way:

Item Front of collector
West tube (F)
Rear of collector
West tube (F)
Temp drop front to back
(F)
Estimated temp of air in tube (F)
Near top 104.1 90.7 13.4 69.4
Mid way down 99 84.9 14.1 62.2
Near bottom 82.9 71.5 11.4 55
         

These show more temperature difference between front and back, but still show pretty good heat transfer around to the back.

Doing the same calculation as above, the relative efficiency of the heat transfer on the back comes out at 0.6 instead of 0.7.

Conclusions?

Basically, it seems to me that while the back and sides of the downspouts run at somewhat cooler temps than the front (as they would have to), the back is still hot enough to contribute substantially to the heat transfer to the air, and that this is a plus for downspout collectors.

To me, this does not necessarily mean its the "best", as other collector designs have their own ways of providing good heat transfer, but it certainly is a plus for the downspout collector. 

If I had just a bit more curiosity, I'd try the same thing with 3 columns of pop cans.  I have a feeling that because the pop can aluminum is so thin, that they don't get as much heat around to the back? 

Do you agree?  I'd like to hear any comments, corrections, suggestions...

 

Gary April 12, 2011